The parameters of SG-1000KVA three-phase isolation transformer:
SG-1000KVA three-phase isolation transformer is the factory’s reference to international similar products that in line with IEC60076-11 and GB6450 and other international and national standards, the winding adopts the method of complete tire winding. SG-1000KVA three-phase isolation transformer are vacuum dipped to achieve transformer insulation class H and product performance to international advanced levels.
The features of SG-1000KVA three-phase isolation transformer
Establishing a new neutral-grounding in the isolation transformer can relieve the common mode interference and other neutrals in the power grid. The SG-1000KVA three-phase isolation transformer converts the three-wire △ wiring into a four-wire Yo system and the shielding further eliminates the high-frequency pulse interference coupled by the internal transformer and noise, although the shielded isolation transformer can effectively prevent interference (pulse and high frequency noise) from various NG, the transformer must be properly grounded and very strict, otherwise the common mode interference will be ineffective.
The advantages of SG-1000KVA three-phase isolation transformer
1. High isolation
2 .Good performance of N-G
3. High common mode interference suppression
4. Convert △ to Y
5 .Voltage taps are easy to convert
6. Designed according to user’s special performance requirements
The technical index of SG-1000KVA three-phase isolation transformer
1. Model: SG-1000KVA Capacity: 1000KVA
2. Input rated voltage: three-phase 380V input rated current: 1519A
Output rated voltage of SG-1000KVA three-phase isolation transformer: 220V
output current of SG-1000KVA three-phase isolation transformer: 2624A
3. No-load current: <12A
4. Impedance; : <5%
5. Load loss: <2080W
6. Working frequency: 50Hz-60Hz
7. Efficiency: ≥95%
8. Temperature rise: <60K
9. Waveform distortion: <0.1%
10. High voltage test of SG-1000KVA three-phase isolation transformer: 2500V, no breakdown in 1 minute
11. Insulation resistance: winding resistance to ground insulation resistance ≥500M Europe
12. Primary to secondary insulation resistance ≥500M Euro
13. Overload capacity: 2 times rated current 1min without abnormal
14. Material of SG-1000KVA three-phase isolation transformer: copper core
15. Insulation class: H class
16. Connection method: Dyn11,
17. Noise <65Db
18. Protection class IP54 / IP20
19. Cooling method
20. Transformer weight :2200KG
21. Overall dimensions 1600 * 1000 * 1800
The conditions using of SG-1000KVA three-phase isolation transformer:
1. Applicable altitude: ≤5000m
2. Ambient temperature: -15 ℃ ~ + 45 ℃
3 .Relative humidity: ≤90%
4. The installation site of SG-1000KVA three-phase isolation transformer should be free of gases, steam, chemical deposits, dirt, conductive dust, conductive dust and other materials that seriously affect the insulation strength of the transformer.